Product Detail: |
DXXD Series Bipolar Linear External Control Power Supply
Model: DXXD series
DXXD Series Bipolar Linear External Control Power Supply
DXKD series unipolar DC power supplies are high performance DC power supplies, specially researched and developed for industrial applications. They have features of high accuracy, high stability, over-voltage protection and over temperature protection. DXKD series power supplies install voltage regulating device and current regulating device, easy to operate.
Product features
- The circuit form of DXXD series DC stabilized voltage and current power supplies is linear series adjustable type, with high stabilization accuracy and low ripple voltage;
- Adopt reference voltage suspension superposition technique, the output voltage can be adjusted from zero to the rated value and output current can be preset from zero to the rated value;
- The status of constant voltage (CV) and constant current (CC) automatically converted;
- Low-power products use a relay to change the AC voltage at the both ends of the rectifier bridge, reducing the tube voltage drop of transistor to improve the overall efficiency;
- High voltage and high current products use SCR phase-shift pre-regulated technology to improve the overall efficiency;
- The output voltage of over-voltage protection is adjustable, when over voltage output, the power supply will turned off output automatically and locked;
Specifications of Bipolar Linear External Control Power Supply
Model |
Power |
Current |
Voltage |
Model of applied electromagnet |
DXXD-300 |
0.3KW |
0.01A~10A |
0.01V~30V |
50 |
DXXD-600 |
0.6KW |
0.01A~10A |
0.01V~60V |
60, 80 |
DXXD-1300 |
1.3KW |
0.01A~10A |
0.1V~130V |
100 |
DXXD-2000 |
2.0KW |
0.01A~16A |
0.1V~125V |
100 |
DXXD-3750 |
3.8KW |
0.01A~25A |
0.1V~150V |
130 |
DXXD-6000 |
6.0KW |
0.01A~40A |
0.1V~150V |
175 |
DXXD-8000 |
8.0KW |
0.01A~50A |
0.1V~160V |
178, 200 |
DXXD-10K |
10.0KW |
0.01A~50A |
0.1V~200V |
200, 220 |
DXXD-12K |
12.0KW |
0.01A~60A |
0.1V~200V |
250, 280 |
DXXD-15K |
15.0KW |
0.01A~75A |
0.1V~200V |
300 |
DXXD-20K |
20.0KW |
0.01A~80A |
0.1V~250V |
380 |
DXXD-30K |
30.0KW |
0.1A~120A |
0.1V~250V |
400 |
Special specifications can be customized according to user’s requirements
Technical indexes of Bipolar Linear External Control Power Supply:
Item |
Parameters |
AC Input |
Single phase AC220V±10% (10KW and below) |
Three phase AC380V±10% (above 10KW) | |
50Hz/60Hz | |
Output Voltage |
0-rated voltage |
Output Current |
0-rated current |
Output Power |
Rated power |
Output-voltage Stability |
≦0.2%+10mV |
Load Stability |
≦0.3%+30mV |
Voltage Ripple |
≤0.2%+10mV (rms) |
Voltage Values Display |
3 1/2 digits meter Accuracy: ±1% +1 word (10%-100% rated value) |
Display Format: 0.000V-9.999V; 0.00V-99.99V; 0.0V-999.9V | |
Current Value Display |
3 1/2 digits meter Accuracy: ±1% +1 word (10%-100% rated value) |
Display Format: 0.000A-9.999A; 0.00A-99.99A; 0.0A-999.9A | |
Over Voltage Protection |
With OVP inside, the protective value is ±5% of rated value; the output will be turned off after protection. |
Over Current Protection |
Over load and over current protection |
Over Temperature Protection |
With OTP inside, the protective value is 85℃±5% (heat sink temperature); the output will be turned off after protection. |
Voltage Setting |
Potentiometer to adjust |
Current Setting |
Potentiometer to adjust |
Output Polarity |
Output positive (+) and negative (-) can be arbitrary grounding |
Heat-dissipating method |
Forced air cooling |
Operational Environment |
Temperature: 0℃~40℃; Humidity: 10%~85% RH |
Storage Environment |
Temperature: -20℃~70℃; Humidity: 10%~90% RH |
Note: all values are the typical values, so under the condition of different load or other conditions it will exceed this value. The accuracy is measured in the state of voltage detection of load terminal, the possible deviation between actual value and the rating under the condition of temperature error and element aging. |